{"product_id":"honeywell-l8148a1017","title":"Honeywell L8148A1017 Immersion Aquastat Relay, 140–240°F High Limit, 120 V","description":"\u003cp\u003eThe L8148A1017 is an immersion Aquastat relay for hydronic boilers that pairs a high limit with the switching relay for the burner and circulator. Its built-in transformer feeds a 24 V AC thermostat circuit, while the burner and pump switch at 120 V AC. Spare terminals take a remote low limit. Install it only on systems that have a pressure relief valve.\u003c\/p\u003e\n\u003ch3\u003eHighlights\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eBurner and circulator contacts are each rated 7.4 A full load and 44.4 A locked rotor at 120 V AC.\u003c\/li\u003e\n\u003cli\u003eThe bulb goes into a Honeywell immersion well with a 1\/2 or 3\/4 in. NPT spud, which is sold separately.\u003c\/li\u003e\n\u003cli\u003eThe differential is fixed at 8°F, and the room thermostat's heat anticipator should be set to 0.2 A.\u003c\/li\u003e\n\u003cli\u003eThe gray enamel horizontal case has 1\/2 in. conduit knockouts and wrap-around terminals for copper wire.\u003c\/li\u003e\n\u003cli\u003eUL listed under MP466 and CSA certified under LR1620.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eIn the box\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eL8148A1017 Aquastat relay\u003c\/li\u003e\n\u003cli\u003eWell adapter\u003c\/li\u003e\n\u003cli\u003eTube of heat conductive compound\u003c\/li\u003e\n\u003cli\u003eRange stops\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":67655293272342,"sku":"Honeywell L8148A1017","price":264.49,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1012\/2163\/0230\/files\/honeywell-l8148a1017-1.webp?v=1791714329","url":"https:\/\/bridgecoreassist.com\/products\/honeywell-l8148a1017","provider":"Bridgecore Assist","version":"1.0","type":"link"}